A Bus segment means a physical connection from the Busmaster to a fieldbus system (eBus / Modbus). Normally this is a serial interface (COM1, COM2, …) or a tcp address. In the Busmaster-website, the Bus segments are associated logical to a Location. The Expert mode in a Bus segment for example allows to run a Firmware-Update for eBus devices.

You can find Bus devices with the selection of the respective Bus segment.

After select a Location, the configuration-website lists the already defined Bus segments. With the button  , you can see further information of status and version.

Add Bus segment

  • Navigate to a Location in the Busmaster-Website.
  • Use the button 
  • Chose a type:
     

    Protocol

    Bus-System

    Description / Using

    eBus KBR TCP eBus device with integrated TCP interface, e.g. multimess F96-…-ET.
    Further information: Name, TCP address, TCP-Port.
    eBus Com-Server Gateway from TCP to serial RS 485 e.g. multisys D2-ESET.
    Further information: Name, TCP address, TCP-Port.
    eBus Serielle Schnittstelle Serial eBus device (RS485) to Com-Port from Busmaster.
    Further information: Name, Com-Port.
    Modbus* Modbus TCP Modbus device with integrated Modbus TCP interface.
    Further information: Name, TCP address, TCP-Port.
    Modbus* Modbus RTU Serial Modbus device to a TCP Gateway.
    Further information: Name, TCP address, TCP-Port.
    Modbus* Modbus RTU Serial Modbus device (RS485) to Com-Port from Busmaster.
    Further information: Name, Com-Port.
    Beliebig* OPC 2.0 DA Any device, which are provided via a OPC 2.0 DA Server.
    Further information: Name, TCP address/ Host-Name, ProgID.
    Virtuelle KBR Geräte* Device, which provides further virtual KBR devices.
    Further information: Name, TCP address.
    *This option is only available by Busmaster and not available in visual energy Starter